Jump to content

Manufacturer-neutral system configuration based on IEC 61850-6

Fast facts

  • Further publishers

    • Jan Arph
    • Eckhard Hermans
    • Martin Hölscher
    • Peter Rümenapp
  • Publishment

    • 2005
  • Anthology

    Herstellerneutrale Systemkonfiguration auf Basis IEC 61850-6 (Internationaler ETG-Kongress 2005)

  • Organizational unit

  • Subjects

    • General electrical engineering
  • Publication format

    Conference paper

Quote

Harnischmacher, Georg et al. 2005. Manufacturer-neutral system configuration based on IEC 61850-6. International ETG Congress 2005, n.n.

Content

Among other things, the IEC 61850 system standard standardizes the configuration language for substation control systems. The SCT (Substation Configuration Tool) tool presented in this article enables manufacturer-independent system project planning on this basis, starting with the graphical input of the primary technology through the modeling of system components ("intelligent electronic devices", IEDs), the generation and type management of abstract function nodes and data objects to the linking of the system model and system components. This is the first time that a target system-independent project planning approach has been developed that enables standard-compliant project preparation with the generation of testable configuration data for substation control systems that can be processed directly in the engineering process, particularly for users and service providers.

Notes and references